• 4 digital inputs NPN, PNP, voltage free • The 4 inputs can be configured as contact or counter • DC power supply • 2-DIN housing • LED indication for power supply, Dupline® bus, input activated • Connection to other cabinet modules via local bus
By buying this product you can collect up to 11
loyalty points.
Your cart will total 11
points that can be converted into a voucher of
5,50 kr.
• 4 digital inputs NPN, PNP, voltage free • The 4 inputs can be configured as contact or counter • DC power supply • 2-DIN housing • LED indication for power supply, Dupline® bus, input activated • Connection to other cabinet modules via local bus
This is an input module for 4 NPN/PNP/voltage free configurable inputs that can also be used as counters of pulses. The configuration of the type of input, digital or counter, is done via the configuration tool and the counted values are stored in the flash memory. The status of every input is indicated by the relevant LED. The 4 inputs are galvanically insulated from the Dupline® bus.
Mode of Operation
The SH2INDI424 has 4 inputs that can be used as digital inputs or as pulse counters. The selection between the two is done via the SH tool. Each input has its own counting value that is stored into the flash memory of the module. This value is read by the controller SH2WEB24 and then used as defined in the SH tool. Coding/Addressing No addressing is needed since the module is provided with a specific identification number (SIN): the user has only to insert the SIN number in the configuration tool when creating the system configuration. Used channels: 4 input channels.
LEDs Indication
Green LED: Power status. ON: supply ON OFF: supply OFF. Yellow LED: Dupline LED If the Dupline® bus is working properly, it is always ON. If there is a fault on the bus, it will be flashing. It is OFF, if the bus is OFF or not connected. Red LEDs: Input status In1: Input activated. This LED is ON if input I1 is ON. In2: Input activated. This LED is ON if input I2 is ON. In3: Input activated. This LED is ON if input I3 is ON. In4: Input activated. This LED is ON if input I4 is ON.
For Controller UWP 3.0 - SH2WEB24 - SB2WEB24 - SA2WEB24
Address assignment Automatic: the controller recognises the module through the SIN (Specific Identification Number) UWP 3.0 og Sx2WEB24
Weight 160g
Forside IP50
Screw terminal IP 20
Beskyttelsesgrad 2 (IEC 60664-1, par. 4.6.2)
Operating temperature -20° til +50°C
Storage temperature -50° til +85°C
Humidity (non-condensing) 20 til 80% RH
Datasheet / Manual Download Data Sheet / Manual - click on the tab Download